3ZZ9990516EG seriesEG301AEG381A, EG381AEEG511A, EG511AEEG711A, EG711AEEG781A, EG781AEEGsériesEG301AEG381A, EG381AEEG511A, EG511AEEG711A, EG711AEEG781A
−5−ENGLISHControl panelFuel tankFuel gaugeEngine switchRecoil starter handleChoke leverOil gauge (oil filler)Spark plug capAir cleanerMufflerTank capR
−6−ïEG301AEG511A, EG511AEEG711A, EG711AEEG781A, EG781AEEG381A, EG381AEPilot lampAC receptacle 20AEarth (ground)terminalAC circuit breakerAC circuit br
4. PRE-OPERATION CHECKS−7−ENGLISHUpper levelOil filler cap(Oil gauge)Lower levelCHECK ENGINE OILBefore checking or refilling oil, be suregenerator is
−8− Check fuel level at fuel level gauge. If fuel level is low, refill withunleaded automotive gasoline. Be sure to use the fuel filter screenon the f
−9−ENGLISHCHECKING COMPONENT PARTSCheck following items before starting engine: Fuel leakage from fuel hose, etc. Bolts and nuts for looseness. Compon
−10−GROUNDING THEGENERATOR To ground the generator to the earth,connect the grounding lug of the generator to the grounding spikedriven into the earth
5. OPERATING PROCEDURES−11−ENGLISH(a) Turn the Engine switch to the position"ON".(b) Turn the AC circuit breaker to theposition "OFF&qu
−12−Pull briskly(e) [Recoil starter model]Pull the starter handle slowly untilpassing the compression point(resistance will be felt), then return the
−13−ENGLISH(g) After the engine started, return thechoke lever gradually to "OPEN"position.Choke leverCLOSEOPEN(h) Warm up the engine withou
−14−(a) Make sure the pilot lamp is turned on.(b) Turn off the switch (es) of the electricalappliance (s) before connecting to thegenerator.(c) Insert
AIR INDEXDescriptive Term Applicable to Emissions Durability PeriodModerate - 50 hours (engine from 0 to 80 cc)125 hours (engine greater than 80 cc
−15−ENGLISHTABLE 1NOTE :When the AC circuit breaker turns off during operation, the generator is overloaded or the appliance is defective. Stop the ge
−16−(d) Turn the AC circuit breaker to theposition "ON".(e)Turn on the switch of the appliance.ONONOFFGFCI RECEPTACLEAfter starting the engi
−17−ENGLISHSwitch position Lower Voltage Receptacle Higher Voltage Receptacle120V Activated full rated output N.A120/240V Activated half of rated outp
−18−(2) DC APPLICATION (Only for charging 12 volt battery) DC receptacle (Only for charging 12 voltbattery) For charging 12 voltage battery, 12V-8.3A(
−19−ENGLISH Do not use both AC and DC output at the same time. Install correct positive (red) or negative (black) cable to the correctpolarity on the
−20−STOPPING THE GENERATOR(a) Turn off the power switch of theelectric equipment and unplug the cordfrom receptacle of the generator.(b) Turn the AC c
6. WATTAGE INFORMATION−21−ENGLISHSome appliances need a "surge" of energy when starting. This means that the amount of electrical power need
VOLTAGE DROP IN ELECTRIC EXTENSION CORDSWhen a long electric extension cord is used to connect an appliance or tool to thegenerator, a certain amount
7. SPARK ARRESTER−23−ENGLISHIn a dry or wooded area, it is recommendable to use the product with a spark arrester.Some areas require the use of a spar
DAILY INSPECTIONBefore running the generator, check the following service items:Excessive vibration,noiseClean air cleaner elementSafe surroundingsEno
EG781AE ce_GU6837 10.1.25 1:36 PM ページ002
−25−ENGLISH*Note: 1. Initial oil change should be performed after first twenty (20) hours of operation.Thereafter change oil every hundred (100) hours
ENGINE OIL CHANGE Change engine oil every 100 hours.(For new engine, change oil after 20hours.)(a) Drain oil by removing the drain plugand the oil fil
−27−ENGLISHCLEANING AND ADJUSTINGSPARK PLUG(a)If the plug is contaminated with carbon,remove it using a plug cleaner or wirebrush.(b) Adjust the elect
−28−This is done because if the length of thebrush gets any shorter, its contactpressure with the slip ring will decrease, resulting in a drop in gene
−29−ENGLISHBrush Maintenance Essentials (Disassembly and Assembly)Disassembly 1. Remove the two flange bolts (M5 x 20),then remove the bracket cover.
10. PREPARATION FOR STORAGE−30−The following procedures should be followed prior to storage of your generator forperiods of 6 months or longer. Drain
11. TROUBLESHOOTING−31−ENGLISHWhen generator engine fails to start after several attempts, or if no electricity isavailable at the output socket, chec
12. WIRING DIAGRAM−32−PLAC winding 2AC winding 1YYGrn/YOrgY/RBlkRR RBlu BluGryGrn/YGrn/YBlkIgnition coilOil sensor switch Spark plugOil sensor unitYBl
−33−ENGLISHPLAC winding 2AC winding 1YYGrn/YOrgY/RBlkRRRBlu BluGryGrn/Y Grn/YBlkIgnition coilOil sensor switch Spark plugOil sensor unitYBlkWWWBrnYYBl
−34−OrgY/RBlkBlkIgnition coilOil sensor switch Spark plugOil sensor unitYAC winding 2AC winding 1YYGrn/YBrnYYBrnBrnYBluBluBrnROTOR STATORSlip ringSub
ENGLISHFOREWORDThank you for purchasing a Makita generator.This manual covers operation and maintenance of the Makita generators.All information in th
−35−ENGLISHPLACwinding 2ACwinding 1Grn/YOrgY/RBlkRRBluBluGryGrn/YGrn/YBlkIgnition coilOil sensor switch Spark plugOil sensor unitYBlkWWWBrnBluBluBluBl
−36−PLGENERATORCONTROL BOXENGINEOrgY/RBlkBlkIgnition coilOil sensor switch Spark plugOil sensor unitYACwinding 2ACwinding 1BluBluGrn/YBrnBluBluRGrnGrn
Makita Corporation3-11-8, Sumiyoshi-choAnjo, Aichi 446-8502 JapanISSUE EMD-GU7037PRINTED IN JAPANMay 2010 IMPRESO EN JAPÓNMayo 2010
CONTENTS1. SAFETY PRECAUTIONS・・・・・・・・・・・・・・・・12. SPECIFICATIONS・・・・・・・・・・・・・・・・・・・33. COMPONENTS・・・・・・・・・・・・・・・・・・・・44. PRE-OPERATION CHECKS・・・・・・・・・・
1. SAFETY PRECAUTIONS−1−ENGLISHPlease make sure you review each precaution carefully.Do not operate the generator near gasoline or gaseous fuel becaus
−2−Do not contact the generator to a commercial power line. Connection to a commercialpower line may short circuit the generator and ruin it or cause
2. SPECIFICATIONS−3−ENGLISHMODELTypeStarting systemLmmmmmmmLLkgModelTypeVoltage regulating systemVA (W)Rated outputRated current AC Output Rated volta
3. COMPONENTS−4−Fuel tankFuel gaugeEngine switchChoke leverOil drain plugOil gauge (oil filler)Spark plug capAir cleanerExhaust outletTank capFuel str